Search

CHISEN 6-CNFJ-220 12V 220Ah GEL Solar Storage Battery

QR code
6-CNFJ-220 is a 12V 220Ah GEL Solar Storage Battery from CHISEN for Solar Off-Grid & Residential Storage: 1500+ cycles at 50% DoD, 12-year float design life.
产品详情

CHISEN 6-CNFJ-220 12V 220Ah GEL Storage Battery | PV / Wind / Micro-grid Storage | OEM Factory Direct

Standard: GB/T 22473.1-2021 Batteries for energy storage — Part 1: Technical conditions for PV off-grid application | Designed and manufactured to standard requirements

30-Second Overview of CHISEN 6-CNFJ-220

Model: 6-CNFJ-220 (12V, 220Ah (10hr))

Technology: GEL VRLA, GEL 12V storage series (12V 38-250Ah)

Highlights: 1500+ cycles @50% DoD (GEL) / 12 years (20°C float)

Typical use: solar off-grid / wind / residential ESS / C&I solar+storage

§1. Product Definition and Four Core Advantages

CHISEN 6-CNFJ-220 is a 12V 220Ah (10hr) valve-regulated lead-acid (VRLA) battery.

Technology: GEL electrolyte with nano-silica GEL immobilisation, 99.99% pure lead, Pb-Ca alloy grid, ABS engineering housing and sealed valve-regulated construction (full standards in §4).

Configuration: 6-CNFJ-220 is a 12V unit — 12V ( units) — for solar off-grid / wind / residential ESS / C&I solar+storage.

CHISEN has focused on VRLA batteries for 20+ years with an export-oriented model, serving 60+ countries (Europe / North America / Middle East / Africa / Latin America / Southeast Asia / Oceania). OEM/ODM service covers telecom, power, data centre, PV, railway and medical customers.

Four core advantages:

1. GEL electrolyte technology: immobilized nano-silica GEL that does not flow, eliminating leakage risk and extending service life.

2. M8 copper-insert terminal (torque 8-10 N·m) terminal (torque per datasheet): vibration and corrosion resistant; supports 800A short-time discharge, suitable for outdoor industrial sites.

3. 12V 220Ah long life: 12 years (20°C float) design life and 1500+ cycles @50% DoD (GEL).

4. Built to GB/T 22473.1-2021 (Batteries for energy storage — Part 1: Technical conditions for PV off-grid application); the standard's requirements for solar off-grid / wind / residential ESS / C&I solar+storage are met by design.

The 2021 edition took effect on 2022-07-01 and supersedes the 2008 edition.

§2. Key Specifications

The table below is the quick-reference specification for 6-CNFJ-220 (standards in §4, applications in §7, float voltage in §12).

Parameter

Value

Model

6-CNFJ-220

Series

GEL 12V storage series (12V 38-250Ah)

Nominal voltage

12V

Rated capacity

220Ah (10hr)

Dimensions (L×W×H)

525×268×220 mm

Total height (with terminal)

225 mm

Approx. weight

62.5 kg (±2%)

Terminal

M8 copper-insert terminal (torque 8-10 N·m)

Housing

ABS engineering plastic

Discharge rate

C10 (10-hour rate)

Float voltage (25°C)

13.6-13.8V (2.27-2.30V/cell), -3mV/°C/cell

Equalize voltage (25°C)

14.4-14.7V (2.40-2.45V/cell), -5mV/°C/cell

Max. charge current

25.0A (0.25C)

Internal resistance

approx. 2.3 mΩ (1kHz, 25°C, fully charged)

Short-circuit current

approx. 5280A (estimated from 1kHz AC resistance, not a test value)

Float design life

12

Cycle life

1500+ cycles @50% DoD (GEL)

Standard

GB/T 22473.1-2021 (Batteries for energy storage — Part 1: Technical conditions for PV off-grid application)

Certification

Third-party inspection/testing on request

System voltages

12V/48V/96V/240V

Applications

solar off-grid / wind / residential ESS / C&I solar+storage

 

§3. Model Nomenclature

Model designation follows the applicable national standard numbering method. Full meaning of 6-CNFJ-220 = 6 cells in series (12V) + VRLA + GEL type + rated capacity 220Ah.

Field

Meaning

Description

6

Number of cells in series

6 × 2V cells = 12V

CN / GFM / FA / HR / FM

Product family

CN = storage VRLA; GFM = stationary float; FA = front terminal; HR = high rate; FM = small sealed

J (if present)

GEL type

J suffix = nano-silica GEL; without J the electrolyte is dilute acid in AGM

220

Rated capacity

Capacity at the 10hr (or 20hr) rate

 

§4. Applicable Standards

CHISEN 6-CNFJ-220 is designed against the following standards:

Standard

Title

Type

Level

Use

GB/T 22473.1-2021

Batteries for energy storage — Part 1: Technical conditions for PV off-grid application

National

GB (recommended)

Domestic sales, customs clearance, tendering

IEC 60896-21:2004

Stationary lead-acid batteries — Part 21: Valve regulated types — Methods of test

International

IEC

Export projects, global tendering

IEC 60896-22:2004

Stationary lead-acid batteries — Part 22: Valve regulated types — Requirements

International

IEC

International customer acceptance

IEC 61427-1:2013

Secondary cells and batteries for renewable energy storage — Part 1: General requirements and methods of test

International

IEC

—

 

Note: third-party inspection and destination-country approval are handled on request. Standard numbers are for design and procurement reference; if a project requires a conformity statement, please provide the corresponding test report for the model.

§5. Physical Construction and Materials

CHISEN 6-CNFJ-220 construction (VRLA sealed design + GEL technology):

Positive plate:

Pb-Ca/Sn-Ca alloy grid with 4BS crystal active material; plate thickness 1.5-5mm by capacity class; high active-material utilization over service life.

Negative plate:

Pb-Ca alloy grid with carbon black and humic acid additives; high hydrogen overpotential, low gassing during charge.

Separator:

Microporous separator matched to the GEL electrolyte, 1.5-3mm, prevents dendrite short circuits.

Electrolyte:

Nano-silica GEL (fumed SiO2 immobilized dilute sulfuric acid), no flow, no acid stratification.

Housing:

ABS engineering plastic, impact and corrosion resistant; wall thickness 2.5-5mm by capacity class.

Lid:

ABS lid with double seal (epoxy resin + rubber ring), leak-free.

Terminal:

M8 copper-insert terminal (torque 8-10 N·m), tin-plated copper core, low contact resistance.

Safety valve:

Silicone one-way valve, opening 10-35 kPa, closing 5-15 kPa, automatic pressure regulation.

Dilute sulfuric acid density: 1.28-1.32 g/cm³ at 25°C, prepared with high-purity deionized water.

GEL VRLA vs flooded: flooded batteries need periodic water topping-up (every 3-6 months), the electrolyte evaporates and self-discharge is high. GEL VRLA is maintenance-free, gas recombination ≥99%, self-discharge <2%/month, deep-discharge recovery is better than AGM (for GEL) with no acid stratification, and no water is ever added — ideal for cyclic storage and unattended sites.

§6. Series Capacity Range

Capacity table for the CHISEN 6-CNFJ-220 family (VRLA, 12V 38-250Ah, 12 models).

No.

Model

V

Ah

L mm

W mm

H mm

Total H mm

kg

Terminal

1

6-CNFJ-38

12

38

197

165

176

176

12.25

M6 copper-insert terminal

2

6-CNFJ-50

12

50

350

167

180

180

18.5

M6 copper-insert terminal

3

6-CNFJ-65

12

65

350

167

180

180

20.0

M6 copper-insert terminal

4

6-CNFJ-80

12

80

330

171

215

220

25.5

M6 copper-insert terminal

5

6-CNFJ-90

12

90

330

171

215

220

27.0

M6 copper-insert terminal

6

6-CNFJ-100

12

100

330

171

215

220

28.65

M8 copper-insert terminal

7

6-CNFJ-120

12

120

408

177

224

224

34.65

M8 copper-insert terminal

8

6-CNFJ-150

12

150

483

170

240

240

42.9

M8 copper-insert terminal

9

6-CNFJ-180

12

180

520

240

217

222

54.49

M8 copper-insert terminal

10

6-CNFJ-200

12

200

520

240

217

222

57.3

M8 copper-insert terminal

11

6-CNFJ-220

12

220

525

268

220

225

62.5

M8 copper-insert terminal

12

6-CNFJ-250

12

250

525

268

220

228

67.7

M8 copper-insert terminal

 

Models can be connected in series/parallel to build the required system voltage. For a GEL version, state the J suffix when ordering; AGM and GEL versions share the same external dimensions with a small weight difference.

§7. Main Applications and Reference Cases

CHISEN 6-CNFJ-220 serves the following high-frequency industrial applications (exported to 60+ countries):

Application 1:

solar off-grid / wind / residential ESS / C&I solar+storage

Application 2:

OEM/ODM projects with customer branding

Application 3:

Replacement and retrofit of existing VRLA strings

Application 4:

Tender supply with documentation package

Application 5:

Long-term programme supply with annual frame agreement

 

Case 1 (Southeast Asia, residential)

8,000+ units of 6-CNFJ-220, 5MW; 5 years.

Case 2 (Middle East, PV, storage)

20,000+ units of 6-CNFJ-220, 50MW; -20 to 50°C.

Case 3 (Africa, micro-grid, off-grid)

10,000+ units of 6-CNFJ-220, 3 years.

Case 4 (Northern Europe, wind farm, wind, storage)

5,000+ units of 6-CNFJ-220, 10MW; -20 to 50°C.

Case 5 (Latin America, C&I, OEM)

6-CNFJ-220, 4 years.

§8. Comparison with Alternative Series

Comparison with alternative CHISEN series, to support selection:

Dimension

This series

Compared series

Conclusion

Battery type

deep-cycle storage battery (CNFJ)

float standby battery (GFMJ)

same, replace

Typical applications

PV storage/wind/micro-grid/off-grid

UPS float/IDC/ / DC

storage CNF, float GFM

Design life

float 12 years (20°C) / deep cycling 1500+ cycles @50% DOD

float 10-18 years (float)

GFM floatlifemorelonger (CNF cyclic grid )

Cycle endurance

1500+ cycles @ 50% DOD (deep cycling)

300-500 cycles @ 80% DOD (float)

CNF deep cycling 5 GFM

Float voltage

cycle charging 14.4-14.7V (2.40-2.45V/cell)

float 13.5V (2.25V/cell)

CNFJ deep cyclingduty cycle charging 14.4-14.7V; 13.5V float standby

Grid alloy

deep cyclingactive material + 4BS

thick plate + float Pb-Ca

same

Standard

GB/T 22473.1-2021 (storage )

GB/T 19638.1-2014 ( )

standard system , replace

 

§9. Selection Decision Table

Battery selection recommendations for 6-CNFJ-220 across applications:

Application

Recommended capacity

Recommended series

PV / Wind / Micro-grid Storage

12V 38-250Ah

GEL Storage series

Float standby / UPS

12V 50-200Ah

GFM

Deep-cycle storage

12V 100-250Ah

CNFJ

Telecom cabinet

12V 55-200Ah

FA(G)

High-rate UPS

12V 380-900W

HR

Small sealed equipment

4V/6V/12V 1.3-28Ah

FM

 

§10. Capacity Sizing Formula and Examples

Battery capacity (Ah) = load power (W) × backup time (h) ÷ bus voltage (V) ÷ inverter efficiency ÷ temperature factor

Inverter efficiency: UPS = 0.85 / DC load = 1.0

Temperature factor: 25°C = 1.0 / 35°C = 0.85 / 45°C = 0.70 (high-temperature derating)

Recommended margin: 20-30%

Example 1: (12V system): lighting 12V/60W/8h daily consumption. Capacity = 60×8÷12÷1.0÷1.0 ≈ 40Ah. Recommended: 12V 220Ah ×1 units (at 50% DOD approx. 50Ah)

Example 2: (48V system, 4 in series): telecombase station 48V/500W/8h backup. Capacity = 500×8÷48÷0.85÷1.0 ≈ 98Ah. Recommended: 12V 220Ah ×4 in series (48V)

Multi-rate discharge table (CHISEN datasheet, 25°C):

Discharge time

Discharge current

Capacity (Ah)

Power (W/cell)

1 HR

121A

121Ah

approx. 206.8 W/cell

3 HR

64.46A

193.6Ah

approx. 110 W/cell

5 HR

41.8A

209Ah

approx. 72.6 W/cell

10 HR

22A

220 Ah

approx. 39.6 W/cell

20 HR

11.88A

108 Ah

approx. 19.8 W/cell

 

Free engineering sizing: send system voltage + load power + backup time + operating temperature to sales@chisen.cn and receive an Excel sizing sheet and quotation within 24 hours.

§11. Cycle Life and Total Cost of Ownership

CHISEN 6-CNFJ-220 cycle life: 1500+ cycles @50% DoD (GEL); float standby life 12 years (20°C float).

TCO = initial purchase cost + replacements × purchase cost + maintenance cost − residual value. In cyclic duty the cycle count determines the number of replacements; calculate per project using actual DoD, ambient temperature, charge/discharge strategy and local electricity price.

§12. Float Voltage and Temperature Compensation

Float voltage: 13.6-13.8V (2.27-2.30V/cell), -3mV/°C/cell.

V_float (T) = 2.27V/cell + (-3mV/°C/cell) × (T − 25°C)

Temperature (°C)

Float voltage (V/cell)

12V battery (total voltage)

40°C

2.225 V/cell

13.35V (12V battery)

35°C

2.240 V/cell

13.44V (12V battery)

30°C

2.255 V/cell

13.53V (12V battery)

25°C (nominal)

2.270 V/cell

13.6V (12V battery)

20°C

2.285 V/cell

13.71V (12V battery)

10°C

2.315 V/cell

13.89V (12V battery)

0°C

2.345 V/cell

14.07V (12V battery)

 

Equalize voltage: 14.4-14.7V (2.40-2.45V/cell), -5mV/°C/cell.

Cycle charge voltage: 14.40-14.70V (2.40-2.45V/cell) at 25°C with -5mV/°C/cell compensation; current limited to 0.25C.

Float voltage accuracy requirement: ±1%% (±25mV); float current <5mA/Ah.

§13. Operating Temperature Range

Operating temperature: discharge -25 to +65°C, charge 0 to +40°C (charge is stricter than discharge), storage -20 to +40°C. Optimum 25°C (capacity reference point).

Temperature (°C)

Capacity

Charge / voltage effect

40°C

approx. 105% Cn

Charge voltage compensation -3mV/°C, charge current reduced 10%

35°C

approx. 102% Cn

Float voltage compensation -3mV/°C, life roughly halved

25°C (nominal)

100% Cn

capacity reference point, float voltage 13.6-13.8V (2.27-2.30V/)

15°C

approx. 95% Cn

float voltage 13.70V (2.28V/cell) (temperature compensated)

0°C

approx. 85% Cn

float voltage 14.00V (2.33V/cell), charge efficiency drops

-15°C

approx. 70% Cn

charge acceptance drops, pre-heating recommended

-20°C (discharge limit)

approx. 65% Cn

discharge only, charging prohibited

 

Temperature effect on life: 12 years at 20°C (about 8.5 years at 25°C); float life halves for every 10°C rise: 35°C ≈ 4.2 years / 45°C ≈ 2.1 years.

High altitude: ≤3000m no special treatment; above 3000m derate 8% per 1000m; above 5000m requires customization (low-pressure sealing + reinforced housing).

§14. Self-Discharge and Storage

Self-discharge <2%%/month at 25°C, fully charged.

Storage temperature

Self-discharge

Shelf time + remaining capacity

20°C

below 1.5%/month

12 months without recharge; 80% remaining

25°C

below 2%/month

6-9 months without recharge; 75-80% remaining

35°C

below 3%/month

recharge after 3-6 months; 65-75% remaining

45°C

below 5%/month

recharge after 1-2 months; 60-65% remaining

 

Store fully charged at -20 to +40°C in a dry, ventilated place, away from sunlight and organic solvents. Recharge every 3-6 months (constant voltage, 24h). Batteries stored over 12 months must be capacity-tested before use.

§15. Charge Current and Discharge Cut-off Voltage

Maximum charge current: 25.0A (0.25C).

Recommended charging parameters (GB/T 22473.1 + IEC 61427-1):

Charge mode

Voltage (V/cell)

Recommended / max current

float

2.27V/cell (12V 13.6V)

<0.50A (≈500mA)

equalize (constant-voltage current-limited)

2.40V/cell (12V 14.4V)

0.1C = 22.00A (recommended) / 0.25C = 55.0A (max)

cycle charging

2.40-2.45V/cell

0.2C = 20.00A (PV cycling duty)

charge temperature compensation

-3mV/°C/cell (float) / -5mV/°C/cell (equalize)

—

 

Charging stage table (CHISEN VRLA engineering practice):

Stage

Voltage (25°C)

Current limit

Application

float Float

2.27V/cell (12V 13.6V)

< 0.50A (≈500mA)

standby power / float standby

equalize Equalize

2.40V/cell

≤ 0.25C = 25.0A

monthly / boost for weak cells

cycle charging Cycle

2.40-2.45V/cell

≤ 0.20C = 20.00A

PV storage / deep cycling

Boost (solar backup)

2.40V±0.005V/cell

≤ 0.20C = 20.00A

solar & wind storage (emergency charging)

 

Discharge cut-off voltage: 1.80V/cell (10hr) / 1.75V/cell (5hr) / 1.70V/cell (3hr) / 1.60V/cell (1hr and below). Short-circuit current: approx. 5280A (estimated from 1kHz AC resistance, not a test value).

Discharge current I (A)

Cut-off Vpc

Application

I < 0.05C

≥1.90Vpc

Very low current long discharge (monitoring standby)

0.05C ≤ I < 0.08C

≥1.85Vpc

Low current float standby (alarm systems)

0.08C ≤ I < 0.2C

≥1.80Vpc

10HR standard discharge

0.2C ≤ I < 0.6C

≥1.75Vpc

5HR medium current discharge

0.6C ≤ I < 1.0C

≥1.70Vpc

1HR high current discharge

1.0C ≤ I < 2.0C

≥1.60Vpc

27min high-power pulse discharge (UPS high rate)

I ≥ 2.0C (short circuit)

—

Short-circuit current per datasheet; not a basis for protection sizing

 

End-of-charge criterion: charge current falls below 0.5% of C10.

§16. CHISEN 6-CNFJ-220 OEM/ODM Customization

Housing color:

ABS housing to customer Pantone (standard grey-white + red/blue/green/yellow/orange + custom)

Logo silk-print:

Customer logo printed on the housing (any language)

Laser marking:

Laser marking on the lid side (model / serial / date / customer code / barcode)

Packaging:

Color box + neutral carton; custom logo, color, barcode and security label

Label:

Battery label laid out to customer requirement (any language)

Terminal:

Standard terminal; alternative specifications on request

Sealing:

Triple sealing structure + flame-arresting acid filter

Testing:

Third-party pre-shipment inspection and factory test report on request

MOQ: samples from 1 unit; system string counts — 24V system 2 units / 48V system 4 units / 96V system 8 units / 110V (108V) system 9 units / 220V (216V) system 18 units; bulk from 200 units. Standard stock 7-15 days, OEM 30-45 days.

§17. FAQ

CHISEN 6-CNFJ-220 FAQ (13 items) covering technical parameters, selection, ordering, shipping and after-sales.

1. 6-CNFJ-220 float voltage / charging method?

Float 13.6-13.8V (2.27-2.30V/cell), -3mV/°C/cell with -3mV/°C/cell compensation; equalize 14.4-14.7V (2.40-2.45V/cell), -5mV/°C/cell. Max charge current 25.0A (0.25C).

2. 6-CNFJ-220 life / cycles?

12 years (20°C float); 1500+ cycles @50% DoD (GEL).

3. 6-CNFJ-220 internal resistance / short-circuit current?

approx. 2.3 mΩ (1kHz, 25°C, fully charged); approx. 5280A (estimated from 1kHz AC resistance, not a test value).

4. 6-CNFJ-220 terminal / dimensions / weight?

Terminal M8 copper-insert terminal (torque 8-10 N·m); dimensions 525×268×220 mm (total height 225 mm); weight 62.5 kg (±2%).

5. 6-CNFJ-220 operating temperature / self-discharge?

Discharge -25 to +65°C / charge 0 to +40°C / storage -20 to +40°C; self-discharge <2%/month at 25°C.

6. 6-CNFJ-220 applicable standard?

GB/T 22473.1-2021 — Batteries for energy storage — Part 1: Technical conditions for PV off-grid application.

7. 6-CNFJ-220 installation orientation?

Upright (terminals up) or side-mounted (terminals forward), max tilt 90°. Never charge upside down.

8. 6-CNFJ-220 export documents?

Packing list + commercial invoice + CO + MSDS + sea transport hazard identification report (non-restricted goods, IMDG special provision 238).

9. 6-CNFJ-220 MOQ / lead time?

Samples from 1 unit; bulk from 200 units. Stock 7-15 days, OEM 30-45 days.

10. 6-CNFJ-220 OEM customization?

Housing color, logo, laser marking, packaging, label and terminal; MOQ 200 units.

11. 6-CNFJ-220 warranty?

12 months from commissioning; extension negotiable for tenders.

12. 6-CNFJ-220 price + freight?

EXW factory price; sea freight by destination port (FOB/CIF/DDP). Email sales@chisen.cn.

13. 6-CNFJ-220 factory address?

Production: Suqian, Jiangsu; sales and support: Hangzhou, Zhejiang.

§18. Daily Operation and Maintenance

Following these practices extends service life to 12 years (20°C float):

1. Charger selection

Industrial charger with constant-voltage current limiting and temperature compensation; float 13.6-13.8V (2.27-2.30V/cell), -3mV/°C/cell; equalize 14.4-14.7V (2.40-2.45V/cell), -5mV/°C/cell monthly; maximum charge current 25.0A (0.25C).

2. Installation environment

Battery cabinet/rack, ≥200mm above floor, ≥100mm from walls; -20 to +50°C discharge / 0 to +40°C charge; forced ventilation above 45°C; derate 8% per 1000m above 3000m.

3. Routine inspection

Check terminal torque, housing for swelling/leakage/cracks, cell voltage deviation <±0.05V, housing-to-ambient temperature difference <3°C. VRLA requires no electrolyte check.

4. Long-term storage

Store fully charged at -20 to +40°C, dry and ventilated; recharge every 3-6 months; capacity-test after 6-9 months; downgrade batteries stored over 2 years.

5. Troubleshooting

Capacity drop >20%: equalize 24h then replace; abnormal float voltage: check charger and compensation; swelling/leakage/odour: stop use; abnormal internal resistance >30%: replace the string.

6. First use / idle batteries

Check appearance/voltage/resistance on receipt; float 4-8h before use; for strings, perform matching so voltage deviation <50mV and resistance deviation <15%.

7. Safety

Never bridge terminals with metal tools; no open flame in the charging area; wear goggles and acid-resistant gloves; recycle scrap batteries through licensed facilities.

§18b. Installation Requirements

VRLA batteries are maintenance-free, but spacing, torque, environment and string matching directly affect life and safety. Mandatory checks:

Item

Requirement

Notes

Orientation

Upright or side-mounted, max tilt 90°

Never charge upside down

Position

Accessible for inspection and replacement

Install at the lowest level

Spacing between batteries

≥10 mm (natural convection)

≥15 mm from cabinet walls

Distance from heat sources

≥50 cm

Avoid boiler/transformer heat zones

Distance from wall / floor

≥100 mm / ≥200 mm

Bottom ventilation required

Rack load

≥3× total weight

Reinforce lower levels

 

Terminal tightening torque:

Terminal

Torque

Capacity

M5

2-3 N·m

≤20Ah

M6

6-8 N·m

20-100Ah

M8

8-10 N·m

≥100Ah

M8 high torque

12-14 N·m

2V 500Ah+

F1/F2 fast-on

Tool-free push-in

Small sealed batteries

 

Item

Allowed range

Notes

Ambient temperature

Discharge -25 to +65°C

Out of range reduces performance and life

Charging ambient temperature

Charge 0 to +40°C

Charge acceptance drops at low temperature

Enclosed space

Not in a fully sealed enclosure

Hydrogen accumulation risks rupture

Humidity

≤85% RH (non-condensing)

High humidity causes corrosion and leakage current

Altitude

≤3000m without correction

Above 3000m derate 8% per 1000m

Dust / corrosive gas

Avoid salt mist / acid / alkali / ammonia

Use a protective cabinet

Vibration

Avoid continuous vibration (>2g)

Railway/lift applications need damping pads

 

Item

Specification

Engineering note

Connector material

Tin-plated pure copper (+0.3mm plating)

Prevents oxidation, lowers contact resistance

Connector resistance

≤0.05 mΩ per connection point

Connection drop is the main string loss

Tightening torque

Per terminal type (table above)

Loose: heating; tight: crushed post

Corrosion protection

Conductive paste or heat-shrink sleeve

Reinforced in salt-mist environments

 

Environmental requirements: discharge -25 to +65°C, charge 0 to +40°C, humidity ≤85% RH non-condensing, altitude ≤3000m without correction, no fully sealed enclosure, avoid salt mist / acid / alkali / ammonia and continuous vibration >2g.

String rules: cell voltage deviation <50mV and resistance deviation <15%; same capacity and batch in one string; select connectors for 1C with 1.5× margin; never reverse-connect; float the string 4-8h before commissioning and record cell voltages.

§18c. Factory Acceptance Test — 4 Steps

Run the following 4 steps on receipt (any failure means re-test or return):

Step 1: Appearance and polarity check (random ≥5%)

No cracks/deformation/swelling; terminals free of rust/oxidation; labels complete; polarity markings clear and posts not reversed; quantity matches the packing list.

Step 2: Open-circuit voltage (after ≥6h rest)

OCV 2.02-2.12V per cell (12V battery: 12.1-12.7V; typical 12.1-12.7V for 12V units, 12.4-12.7V for a 12V 100Ah unit). Acceptance: same-batch deviation ≤30mV; 30-50mV re-test; >50mV rejected.

Step 3: Internal resistance (1kHz AC)

Measured value <1.3× datasheet nominal; same-batch deviation <15% . Reference: approx. 2.3 mΩ (1kHz, 25°C, fully charged).

Step 4: Capacity confirmation

Capacity test at the 20hr current (I = 5.40A for a 220Ah (10hr) battery); measured capacity ≥209Ah (95% of rating) accepted, <90% rejected. Charge the battery to full before warehousing.

Record: battery number / date / ambient temperature / OCV / resistance / capacity / conclusion / inspector signature — used for warranty claims and later string matching.

§18d. Safety and Compliance

VRLA batteries are maintenance-free, but hydrogen generation during charging, dilute sulfuric acid corrosion and high-current short-circuit risks require strict rules:

Level

Meaning

Typical situation

DANGER

Can cause injury or death

Sealed enclosure use; non-specified charger; metal tools bridging terminals

WARNING

May cause injury or property damage

Metal enclosure without insulation; near sparks; open flame; reversed polarity

CAUTION

May cause minor injury or damage

Out-of-range temperature; near heat sources; damp environment; direct sunlight

 

Prohibitions:

Prohibition

Requirement

Reason

Mixing chemistries

Do not mix with Ni-MH / Ni-Cd / lithium

Leakage, heating, rupture

Organic solvents

Do not clean with thinner, petrol or grease

Corrodes the housing

Exceeding rated current

Stay within datasheet maximum

Leakage, heating, rupture

Carrying by terminals

Never lift by terminals or cables

Damages the plate group

Stepping on the battery

No heavy objects or standing

Deformation and internal short circuit

 

Application

Requirement

Note

Life-support medical equipment

Requires an independent backup power system

VRLA failure may endanger life

Dialysis equipment

Not recommended

High reliability requirement; professional assessment

Nuclear / defence equipment

Prohibited

Requires dedicated non-VRLA solutions

Automotive / aircraft / rail / marine control

Prohibited

Precision control on moving platforms

Subsea equipment

Prohibited

High humidity and pressure; severe leakage consequences

 

Item

Requirement

Note

Insulated tools

PVC-taped wrench, one terminal at a time

Prevents short circuit across terminals

PPE

Acid-resistant gloves, insulated boots, goggles

Prevents shock, burns and acid splash

Acid contact

Rinse with plenty of water for 15 minutes

Seek medical help; eye splash immediate

Scrap disposal

Licensed recycler per local regulations

Lead recovery >95%; never dismantle

 

Symptom

Immediate action

Note

Swelling / deformation

Stop use and isolate

Precursor to thermal runaway

Leakage / smoke

Cut power, ventilate, evacuate

Acid corrosion + hydrogen; do not wash with water

Odour / abnormal heat

Stop charging, disconnect load

Check charger and polarity

Abnormal cell voltage

Check string balance

Deviation >50mV requires balancing

 

Restricted applications: life-support medical equipment requires an independent backup system; dialysis equipment is not recommended; nuclear/defence, automotive/aircraft/rail/marine control and subsea equipment are prohibited.

Emergency handling: swelling/deformation — stop use and isolate; leakage/smoke — cut power, ventilate, evacuate; odour/abnormal heat — stop charging and disconnect the load; abnormal cell voltage — check string balance.

This section is based on mainstream VRLA safety practice. Site procedures, local regulations (e.g. NFPA 70E / IEC 62485) and contract terms take precedence.

§19. CHISEN® Product Strength and Global Service

1. Product range

20+ years focused on VRLA; 200+ models covering 2V/4V/6V/12V, 1.3-3000Ah; mainstream models in stock, shipment in 7-15 days.

2. Global service

60+ export countries; telecom, power, data centre, PV, railway and medical projects; 7×24 multilingual support (EN/CN/ES/FR/AR/RU/VI).

3. Quality control

100% capacity / resistance / voltage / appearance inspection; SPC on paste mixing, group assembly, formation and sealing; third-party inspection on request.

4. Export support

Commercial invoice, packing list, CO, MSDS, sea transport hazard identification report and factory test report on request.

5. Long-term cooperation

Dedicated technical contact; lead sharing and training for OEM partners; annual rebates, priority supply and new-product trials for strategic customers.

6. Sustainability

Lead recovery >95%; RoHS/REACH declarations on request; destination environmental requirements handled per customer need.

§20. Contact — Reply within 24 Hours

Email: sales@chisen.cn (quotation + sizing within 24h)

Tel / WhatsApp: +86 131 6622 6999

Website: https://www.chisen.cn