CHISEN GFMJ-400 2V 400Ah Float GEL Battery | UPS / Data Center / Telecom | OEM Factory Direct
Standard: GB/T 19638.1-2014 Stationary valve regulated lead-acid batteries — Part 1: Technical conditions | Designed and manufactured to standard requirements
30-Second Overview of CHISEN GFMJ-400
Model: GFMJ-400 (2V, 400Ah)
Technology: GEL VRLA, GEL 2V float series (2V 100-2500Ah)
Highlights: 200-300 cycles @80% DoD / 10-18 years (20°C float)
Typical use: UPS, data centres, telecom DC power
§1. Product Definition and Four Core Advantages
CHISEN GFMJ-400 is a 2V 400Ah valve-regulated lead-acid (VRLA) battery.
Technology: GEL electrolyte with nano-silica GEL immobilisation, 99.99% pure lead, Pb-Ca alloy grid, ABS engineering housing and sealed valve-regulated construction (full standards in §4).
Configuration: GFMJ-400 is a 2V unit — 12V (6 units) / 48V (24 units) / 110V (55 units) / 220V (110 units) / 380V (190 units) — for UPS, data centres, telecom DC power.
CHISEN has focused on VRLA batteries for 20+ years with an export-oriented model, serving 60+ countries (Europe / North America / Middle East / Africa / Latin America / Southeast Asia / Oceania). OEM/ODM service covers telecom, power, data centre, PV, railway and medical customers.
Four core advantages:
1. GEL electrolyte technology: immobilized nano-silica GEL that does not flow, eliminating leakage risk and extending service life.
2. M8 copper-insert terminal (torque 8-10 N·m) terminal (torque per datasheet): vibration and corrosion resistant; supports 800A short-time discharge, suitable for outdoor industrial sites.
3. 2V 400Ah long life: 10-18 years (20°C float) design life and 200-300 cycles @80% DoD.
4. Built to GB/T 19638.1-2014 (Stationary valve regulated lead-acid batteries — Part 1: Technical conditions); the standard's requirements for UPS, data centres, telecom DC power are met by design.
§2. Key Specifications
The table below is the quick-reference specification for GFMJ-400 (standards in §4, applications in §7, float voltage in §12).
|
Parameter |
Value |
|
Model |
GFMJ-400 |
|
Series |
GEL 2V float series (2V 100-2500Ah) |
|
Nominal voltage |
2V |
|
Rated capacity |
400Ah |
|
Dimensions (L×W×H) |
195×170×340 mm |
|
Total height (with terminal) |
345 mm |
|
Approx. weight |
25.6 kg (±2%) |
|
Terminal |
M8 copper-insert terminal (torque 8-10 N·m) |
|
Housing |
ABS engineering plastic |
|
Discharge rate |
C10 (10-hour rate) |
|
Float voltage (25°C) |
2.25V/cell, -3mV/°C/cell |
|
Equalize voltage (25°C) |
2.35V/cell, -5mV/°C/cell |
|
Max. charge current |
100A (0.25C) |
|
Internal resistance |
approx. 0.56 mΩ (1kHz, 25°C, fully charged) |
|
Short-circuit current |
approx. 3556A (estimated from 1kHz AC resistance, not a test value) |
|
Float design life |
18 |
|
Cycle life |
200-300 cycles @80% DoD |
|
Standard |
GB/T 19638.1-2014 (Stationary valve regulated lead-acid batteries — Part 1: Technical conditions) |
|
Certification |
Third-party inspection/testing on request |
|
System voltages |
12V/48V/110V/220V/380V |
|
Applications |
UPS, data centres, telecom DC power |
§3. Model Nomenclature
Model designation follows the applicable national standard numbering method. Full meaning of GFMJ-400 = 1 cells in series (2V) + VRLA + GEL type + rated capacity 400Ah.
|
Field |
Meaning |
Description |
|
1 |
Number of cells in series |
1 × 2V cells = 2V |
|
CN / GFM / FA / HR / FM |
Product family |
CN = storage VRLA; GFM = stationary float; FA = front terminal; HR = high rate; FM = small sealed |
|
J (if present) |
GEL type |
J suffix = nano-silica GEL; without J the electrolyte is dilute acid in AGM |
|
400 |
Rated capacity |
Capacity at the 10hr (or 20hr) rate |
§4. Applicable Standards
CHISEN GFMJ-400 is designed against the following standards:
|
Standard |
Title |
Type |
Level |
Use |
|
GB/T 19638.1-2014 |
Stationary valve regulated lead-acid batteries — Part 1: Technical conditions |
National |
GB (recommended) |
Domestic sales, customs clearance, tendering |
|
IEC 60896-21:2004 |
Stationary lead-acid batteries — Part 21: Valve regulated types — Methods of test |
International |
IEC |
Export projects, global tendering |
|
IEC 60896-22:2004 |
Stationary lead-acid batteries — Part 22: Valve regulated types — Requirements |
International |
IEC |
International customer acceptance |
|
GB/T 19638.2-2014 |
Stationary valve regulated lead-acid batteries — Part 2: Product varieties and specifications |
National |
GB/T, 2014 edition, effective 2015-01-22 |
— |
Note: third-party inspection and destination-country approval are handled on request. Standard numbers are for design and procurement reference; if a project requires a conformity statement, please provide the corresponding test report for the model.
§5. Physical Construction and Materials
CHISEN GFMJ-400 construction (VRLA sealed design + GEL technology):
Positive plate:
Pb-Ca/Sn-Ca alloy grid with 4BS crystal active material; plate thickness 1.5-5mm by capacity class; high active-material utilization over service life.
Negative plate:
Pb-Ca alloy grid with carbon black and humic acid additives; high hydrogen overpotential, low gassing during charge.
Separator:
Microporous separator matched to the GEL electrolyte, 1.5-3mm, prevents dendrite short circuits.
Electrolyte:
Nano-silica GEL (fumed SiO2 immobilized dilute sulfuric acid), no flow, no acid stratification.
Housing:
ABS engineering plastic, impact and corrosion resistant; wall thickness 2.5-5mm by capacity class.
Lid:
ABS lid with double seal (epoxy resin + rubber ring), leak-free.
Terminal:
M8 copper-insert terminal (torque 8-10 N·m), tin-plated copper core, low contact resistance.
Safety valve:
Silicone one-way valve, opening 10-35 kPa, closing 5-15 kPa, automatic pressure regulation.
Dilute sulfuric acid density: 1.28-1.32 g/cm³ at 25°C, prepared with high-purity deionized water.
GEL VRLA vs flooded: flooded batteries need periodic water topping-up (every 3-6 months), the electrolyte evaporates and self-discharge is high. GEL VRLA is maintenance-free, gas recombination ≥99%, self-discharge <2%/month, deep-discharge recovery is better than AGM (for GEL) with no acid stratification, and no water is ever added — ideal for cyclic storage and unattended sites.
§6. Series Capacity Range
Capacity table for the CHISEN GFMJ-400 family (VRLA, 2V 100-2500Ah, 15 models).
|
No. |
Model |
V |
Ah |
L mm |
W mm |
H mm |
Total H mm |
kg |
Terminal |
|
1 |
GFMJ-100 |
2 |
100 |
174 |
63 |
337 |
347 |
7.9 |
M8 copper-insert terminal |
|
2 |
GFMJ-200 |
2 |
200 |
200 |
105 |
340 |
345 |
12.9 |
M8 copper-insert terminal |
|
3 |
GFMJ-300L |
2 |
300 |
126 |
187 |
362 |
375 |
19.6 |
M8 copper-insert terminal |
|
4 |
GFMJ-300 |
2 |
300 |
170 |
150 |
340 |
345 |
19.1 |
M8 copper-insert terminal |
|
5 |
GFMJ-400L |
2 |
400 |
166 |
185 |
362 |
375 |
25.7 |
M8 copper-insert terminal |
|
6 |
GFMJ-400 |
2 |
400 |
195 |
170 |
340 |
345 |
25.6 |
M8 copper-insert terminal |
|
7 |
GFMJ-500L |
2 |
500 |
197 |
187 |
362 |
375 |
31.2 |
M8 copper-insert terminal |
|
8 |
GFMJ-500 |
2 |
500 |
240 |
170 |
340 |
345 |
30.1 |
M8 copper-insert terminal |
|
9 |
GFMJ-600L |
2 |
600 |
223 |
185 |
362 |
372 |
35.6 |
M8 copper-insert terminal |
|
10 |
GFMJ-600 |
2 |
600 |
283 |
170 |
340 |
345 |
37.1 |
M8 copper-insert terminal |
|
11 |
GFMJ-800 |
2 |
800 |
382 |
170 |
340 |
345 |
51.7 |
M8 copper-insert terminal |
|
12 |
GFMJ-1000 |
2 |
1000 |
470 |
170 |
340 |
345 |
60.2 |
M8 copper-insert terminal |
|
13 |
GFMJ-1500 |
2 |
1500 |
353 |
335 |
335 |
345 |
87.2 |
M8 copper-insert terminal |
|
14 |
GFMJ-2000 |
2 |
2000 |
475 |
335 |
335 |
345 |
119 |
M8 copper-insert terminal |
|
15 |
GFMJ-2500 |
2 |
2500 |
475 |
335 |
335 |
345 |
130 |
M8 copper-insert terminal |
Models can be connected in series/parallel to build the required system voltage. For a GEL version, state the J suffix when ordering; AGM and GEL versions share the same external dimensions with a small weight difference.
§7. Main Applications and Reference Cases
CHISEN GFMJ-400 serves the following high-frequency industrial applications (exported to 60+ countries):
Application 1:
UPS, data centres, telecom DC power
Application 2:
OEM/ODM projects with customer branding
Application 3:
Replacement and retrofit of existing VRLA strings
Application 4:
Tender supply with documentation package
Application 5:
Long-term programme supply with annual frame agreement
Case 1 (Europe, data center, equipment room, UPS)
760+ cells of GFMJ-400, 380V system; 20 years.
Case 2 (UPS, standby, float)
20,000+ cells of GFMJ-400, 500kVA; 4 years.
Case 3 (Southeast Asia, metro, UPS, float)
55+ cells of GFMJ-400, 110V system; 2.25V system; 5 years.
Case 4 (Middle East, float)
110+ cells of GFMJ-400, 220V system; 2.25V system; 600MW.
Case 5 (Africa, equipment room, telecom operator, UPS)
550+ cells of GFMJ-400, 110V system.
§8. Comparison with Alternative Series
Comparison with alternative CHISEN series, to support selection:
|
Dimension |
This series |
Compared series |
Conclusion |
|
Battery type |
float GEL GEL (GFMJ) |
front-access terminal GEL GEL (FA(G)) |
same GEL GEL VRLA; FA(G) terminal , installation environment |
|
Typical applications |
UPS/IDC/ / |
telecom site/ / |
GFMJ, FA(G) |
|
Design life |
10-18 years (GFMJ float) |
12 years (FA(G) float) |
GFMJ longerlifeslightly |
|
Cycle endurance |
300-500 cycles @ 80% DOD |
300-400 cycles |
deep cycling |
|
Electrolyte |
nano-silica GEL (GEL GEL) |
nano-silica GEL (GEL GEL) |
same GEL GEL , terminal environment |
|
Operating temperature |
-20~50°C |
-20~50°C |
GFMJ wide temperatureslightly |
|
Standard |
GB/T 19638.1-2014 |
DL/T 637-2019 |
standard system same |
§9. Selection Decision Table
Battery selection recommendations for GFMJ-400 across applications:
|
Application |
Recommended capacity |
Recommended series |
|
UPS / Data Center / Telecom |
2V 100-2500Ah |
Float GEL series |
|
Float standby / UPS |
12V 50-200Ah |
GFM |
|
Deep-cycle storage |
12V 100-250Ah |
CNFJ |
|
Telecom cabinet |
12V 55-200Ah |
FA(G) |
|
High-rate UPS |
12V 380-900W |
HR |
|
Small sealed equipment |
4V/6V/12V 1.3-28Ah |
FM |
§10. Capacity Sizing Formula and Examples
Battery capacity (Ah) = load power (W) × backup time (h) ÷ bus voltage (V) ÷ inverter efficiency ÷ temperature factor
Inverter efficiency: UPS = 0.85 / DC load = 1.0
Temperature factor: 25°C = 1.0 / 35°C = 0.85 / 45°C = 0.70 (high-temperature derating)
Recommended margin: 20-30%
Example 1: (220V system, 110 cellsin series): large UPS 220V/20kW/3h backup. Capacity = 20000×3÷220÷0.85÷1.0 ≈ 321Ah. Recommended: 2V 400Ah ×110 in series (220V)
Example 2: (48V system, 24 cellsin series): power DC panel 48V/4kW/4h backup. Capacity = 4000×4÷48÷0.85÷1.0 ≈ 392Ah. Recommended: 2V 400Ah ×24 in series (48V)
Multi-rate discharge table (CHISEN datasheet, 25°C):
|
Discharge time |
Discharge current |
Capacity (Ah) |
Power (W/cell) |
|
1 HR |
220A |
220Ah |
approx. 374.4 W/cell |
|
3 HR |
117.36A |
352Ah |
approx. 199.2 W/cell |
|
5 HR |
76A |
380Ah |
approx. 132.8 W/cell |
|
10 HR |
40A |
400 Ah |
approx. 72 W/cell |
|
20 HR |
20A |
400 Ah |
approx. 37.6 W/cell |
Free engineering sizing: send system voltage + load power + backup time + operating temperature to sales@chisen.cn and receive an Excel sizing sheet and quotation within 24 hours.
§11. Cycle Life and Total Cost of Ownership
CHISEN GFMJ-400 cycle life: 200-300 cycles @80% DoD; float standby life 10-18 years (20°C float).
TCO = initial purchase cost + replacements × purchase cost + maintenance cost − residual value. In cyclic duty the cycle count determines the number of replacements; calculate per project using actual DoD, ambient temperature, charge/discharge strategy and local electricity price.
§12. Float Voltage and Temperature Compensation
Float voltage: 2.25V/cell, -3mV/°C/cell.
V_float (T) = 2.27V/cell + (-3mV/°C/cell) × (T − 25°C)
|
Temperature (°C) |
Float voltage (V/cell) |
2V battery (total voltage) |
|
40°C |
2.205 V/cell |
26.5V (24V systems) |
|
35°C |
2.220 V/cell |
26.6V (24V systems) |
|
30°C |
2.235 V/cell |
26.8V (24V systems) |
|
25°C (nominal) |
2.250 V/cell |
27.0V (24V systems) |
|
20°C |
2.265 V/cell |
27.2V (24V systems) |
|
10°C |
2.295 V/cell |
27.5V (24V systems) |
|
0°C |
2.325 V/cell |
27.9V (24V systems) |
Equalize voltage: 2.35V/cell, -5mV/°C/cell.
Cycle charge voltage: 14.10-14.70V (2.35-2.45V/cell) at 25°C with -5mV/°C/cell compensation; current limited to 0.25C.
Float voltage accuracy requirement: ±1%% (±25mV); float current <5mA/Ah.
§13. Operating Temperature Range
Operating temperature: discharge -25 to +65°C, charge 0 to +40°C (charge is stricter than discharge), storage -20 to +40°C. Optimum 25°C (capacity reference point).
|
Temperature (°C) |
Capacity |
Charge / voltage effect |
|
40°C |
approx. 105% Cn |
Charge voltage compensation -3mV/°C, charge current reduced 10% |
|
35°C |
approx. 102% Cn |
Float voltage compensation -3mV/°C, life roughly halved |
|
25°C (nominal) |
100% Cn |
capacity reference point, float voltage 2.25V/cell |
|
15°C |
approx. 95% Cn |
float voltage 13.70V (2.28V/cell) (temperature compensated) |
|
0°C |
approx. 85% Cn |
float voltage 14.00V (2.33V/cell), charge efficiency drops |
|
-15°C |
approx. 70% Cn |
charge acceptance drops, pre-heating recommended |
|
-20°C (discharge limit) |
approx. 65% Cn |
discharge only, charging prohibited |
Temperature effect on life: 18 years at 20°C (about 12.7 years at 25°C); float life halves for every 10°C rise: 35°C ≈ 6.4 years / 45°C ≈ 3.2 years.
High altitude: ≤3000m no special treatment; above 3000m derate 8% per 1000m; above 5000m requires customization (low-pressure sealing + reinforced housing).
§14. Self-Discharge and Storage
Self-discharge <2%%/month at 25°C, fully charged.
|
Storage temperature |
Self-discharge |
Shelf time + remaining capacity |
|
20°C |
below 1.5%/month |
12 months without recharge; 80% remaining |
|
25°C |
below 2%/month |
6-9 months without recharge; 75-80% remaining |
|
35°C |
below 3%/month |
recharge after 3-6 months; 65-75% remaining |
|
45°C |
below 5%/month |
recharge after 1-2 months; 60-65% remaining |
Store fully charged at -20 to +40°C in a dry, ventilated place, away from sunlight and organic solvents. Recharge every 3-6 months (constant voltage, 24h). Batteries stored over 12 months must be capacity-tested before use.
§15. Charge Current and Discharge Cut-off Voltage
Maximum charge current: 100A (0.25C).
Recommended charging parameters (IEC 60896 + GB/T 19638.2):
|
Charge mode |
Voltage (V/cell) |
Recommended / max current |
|
float |
2.25V/cell |
<2A (≈2000mA) |
|
equalize (constant-voltage current-limited) |
2.35V/cell |
0.1C = 40.00A (recommended) / 0.25C = 100.0A (max) |
|
cycle charging |
2.35-2.45V/cell |
0.2C = 80.00A (PV cycling duty) |
|
charge temperature compensation |
-3mV/°C/cell (float) / -5mV/°C/cell (equalize) |
— |
Charging stage table (CHISEN VRLA engineering practice):
|
Stage |
Voltage (25°C) |
Current limit |
Application |
|
float Float |
2.25V/cell |
< 2.50A (≈2500mA) |
standby power / float standby |
|
equalize Equalize |
2.35V/cell |
≤ 0.25C = 125A |
monthly / boost for weak cells |
|
cycle charging Cycle |
2.35-2.45V/cell |
≤ 0.20C = 100.00A |
PV storage / deep cycling |
|
Boost (solar backup) |
2.35V±0.005V/cell |
≤ 0.20C = 100.00A |
solar & wind storage (emergency charging) |
Discharge cut-off voltage: 1.80V/cell (10hr) / 1.75V/cell (5hr) / 1.70V/cell (3hr) / 1.60V/cell (1hr and below). Short-circuit current: approx. 3556A (estimated from 1kHz AC resistance, not a test value).
|
Discharge current I (A) |
Cut-off Vpc |
Application |
|
I < 0.05C |
≥1.90Vpc |
Very low current long discharge (monitoring standby) |
|
0.05C ≤ I < 0.08C |
≥1.85Vpc |
Low current float standby (alarm systems) |
|
0.08C ≤ I < 0.2C |
≥1.80Vpc |
10HR standard discharge |
|
0.2C ≤ I < 0.6C |
≥1.75Vpc |
5HR medium current discharge |
|
0.6C ≤ I < 1.0C |
≥1.70Vpc |
1HR high current discharge |
|
1.0C ≤ I < 2.0C |
≥1.60Vpc |
27min high-power pulse discharge (UPS high rate) |
|
I ≥ 2.0C (short circuit) |
— |
Short-circuit current per datasheet; not a basis for protection sizing |
End-of-charge criterion: charge current falls below 0.5% of C10.
§16. CHISEN GFMJ-400 OEM/ODM Customization
Housing color:
ABS housing to customer Pantone (standard grey-white + red/blue/green/yellow/orange + custom)
Logo silk-print:
Customer logo printed on the housing (any language)
Laser marking:
Laser marking on the lid side (model / serial / date / customer code / barcode)
Packaging:
Color box + neutral carton; custom logo, color, barcode and security label
Label:
Battery label laid out to customer requirement (any language)
Terminal:
Standard terminal; alternative specifications on request
Sealing:
Triple sealing structure + flame-arresting acid filter
Testing:
Third-party pre-shipment inspection and factory test report on request
MOQ: samples from 1 unit; system string counts — 24V system 2 units / 48V system 4 units / 96V system 8 units / 110V (108V) system 9 units / 220V (216V) system 18 units; bulk from 200 units. Standard stock 7-15 days, OEM 30-45 days.
§17. FAQ
CHISEN GFMJ-400 FAQ (13 items) covering technical parameters, selection, ordering, shipping and after-sales.
1. GFMJ-400 float voltage / charging method?
Float 2.25V/cell, -3mV/°C/cell with -3mV/°C/cell compensation; equalize 2.35V/cell, -5mV/°C/cell. Max charge current 100A (0.25C).
2. GFMJ-400 life / cycles?
10-18 years (20°C float); 200-300 cycles @80% DoD.
3. GFMJ-400 internal resistance / short-circuit current?
approx. 0.56 mΩ (1kHz, 25°C, fully charged); approx. 3556A (estimated from 1kHz AC resistance, not a test value).
4. GFMJ-400 terminal / dimensions / weight?
Terminal M8 copper-insert terminal (torque 8-10 N·m); dimensions 195×170×340 mm (total height 345 mm); weight 25.6 kg (±2%).
5. GFMJ-400 operating temperature / self-discharge?
Discharge -25 to +65°C / charge 0 to +40°C / storage -20 to +40°C; self-discharge <2%/month at 25°C.
6. GFMJ-400 applicable standard?
GB/T 19638.1-2014 — Stationary valve regulated lead-acid batteries — Part 1: Technical conditions.
7. GFMJ-400 installation orientation?
Upright (terminals up) or side-mounted (terminals forward), max tilt 90°. Never charge upside down.
8. GFMJ-400 export documents?
Packing list + commercial invoice + CO + MSDS + sea transport hazard identification report (non-restricted goods, IMDG special provision 238).
9. GFMJ-400 MOQ / lead time?
Samples from 1 unit; bulk from 200 units. Stock 7-15 days, OEM 30-45 days.
10. GFMJ-400 OEM customization?
Housing color, logo, laser marking, packaging, label and terminal; MOQ 200 units.
11. GFMJ-400 warranty?
12 months from commissioning; extension negotiable for tenders.
12. GFMJ-400 price + freight?
EXW factory price; sea freight by destination port (FOB/CIF/DDP). Email sales@chisen.cn.
13. GFMJ-400 factory address?
Production: Suqian, Jiangsu; sales and support: Hangzhou, Zhejiang.
§18. Daily Operation and Maintenance
Following these practices extends service life to 10-18 years (20°C float):
1. Charger selection
Industrial charger with constant-voltage current limiting and temperature compensation; float 2.25V/cell, -3mV/°C/cell; equalize 2.35V/cell, -5mV/°C/cell monthly; maximum charge current 100A (0.25C).
2. Installation environment
Battery cabinet/rack, ≥200mm above floor, ≥100mm from walls; -20 to +50°C discharge / 0 to +40°C charge; forced ventilation above 45°C; derate 8% per 1000m above 3000m.
3. Routine inspection
Check terminal torque, housing for swelling/leakage/cracks, cell voltage deviation <±0.05V, housing-to-ambient temperature difference <3°C. VRLA requires no electrolyte check.
4. Long-term storage
Store fully charged at -20 to +40°C, dry and ventilated; recharge every 3-6 months; capacity-test after 6-9 months; downgrade batteries stored over 2 years.
5. Troubleshooting
Capacity drop >20%: equalize 24h then replace; abnormal float voltage: check charger and compensation; swelling/leakage/odour: stop use; abnormal internal resistance >30%: replace the string.
6. First use / idle batteries
Check appearance/voltage/resistance on receipt; float 4-8h before use; for strings, perform matching so voltage deviation <50mV and resistance deviation <15%.
7. Safety
Never bridge terminals with metal tools; no open flame in the charging area; wear goggles and acid-resistant gloves; recycle scrap batteries through licensed facilities.
§18b. Installation Requirements
VRLA batteries are maintenance-free, but spacing, torque, environment and string matching directly affect life and safety. Mandatory checks:
|
Item |
Requirement |
Notes |
|
Orientation |
Upright or side-mounted, max tilt 90° |
Never charge upside down |
|
Position |
Accessible for inspection and replacement |
Install at the lowest level |
|
Spacing between batteries |
≥10 mm (natural convection) |
≥15 mm from cabinet walls |
|
Distance from heat sources |
≥50 cm |
Avoid boiler/transformer heat zones |
|
Distance from wall / floor |
≥100 mm / ≥200 mm |
Bottom ventilation required |
|
Rack load |
≥3× total weight |
Reinforce lower levels |
Terminal tightening torque:
|
Terminal |
Torque |
Capacity |
|
M5 |
2-3 N·m |
≤20Ah |
|
M6 |
6-8 N·m |
20-100Ah |
|
M8 |
8-10 N·m |
≥100Ah |
|
M8 high torque |
12-14 N·m |
2V 500Ah+ |
|
F1/F2 fast-on |
Tool-free push-in |
Small sealed batteries |
|
Item |
Allowed range |
Notes |
|
Ambient temperature |
Discharge -25 to +65°C |
Out of range reduces performance and life |
|
Charging ambient temperature |
Charge 0 to +40°C |
Charge acceptance drops at low temperature |
|
Enclosed space |
Not in a fully sealed enclosure |
Hydrogen accumulation risks rupture |
|
Humidity |
≤85% RH (non-condensing) |
High humidity causes corrosion and leakage current |
|
Altitude |
≤3000m without correction |
Above 3000m derate 8% per 1000m |
|
Dust / corrosive gas |
Avoid salt mist / acid / alkali / ammonia |
Use a protective cabinet |
|
Vibration |
Avoid continuous vibration (>2g) |
Railway/lift applications need damping pads |
|
Item |
Specification |
Engineering note |
|
Connector material |
Tin-plated pure copper (+0.3mm plating) |
Prevents oxidation, lowers contact resistance |
|
Connector resistance |
≤0.05 mΩ per connection point |
Connection drop is the main string loss |
|
Tightening torque |
Per terminal type (table above) |
Loose: heating; tight: crushed post |
|
Corrosion protection |
Conductive paste or heat-shrink sleeve |
Reinforced in salt-mist environments |
Environmental requirements: discharge -25 to +65°C, charge 0 to +40°C, humidity ≤85% RH non-condensing, altitude ≤3000m without correction, no fully sealed enclosure, avoid salt mist / acid / alkali / ammonia and continuous vibration >2g.
String rules: cell voltage deviation <50mV and resistance deviation <15%; same capacity and batch in one string; select connectors for 1C with 1.5× margin; never reverse-connect; float the string 4-8h before commissioning and record cell voltages.
§18c. Factory Acceptance Test — 4 Steps
Run the following 4 steps on receipt (any failure means re-test or return):
Step 1: Appearance and polarity check (random ≥5%)
No cracks/deformation/swelling; terminals free of rust/oxidation; labels complete; polarity markings clear and posts not reversed; quantity matches the packing list.
Step 2: Open-circuit voltage (after ≥6h rest)
OCV 2.02-2.12V per cell (2V battery: 2.0-2.1V; typical 12.1-12.7V for 12V units, 12.4-12.7V for a 12V 100Ah unit). Acceptance: same-batch deviation ≤30mV; 30-50mV re-test; >50mV rejected.
Step 3: Internal resistance (1kHz AC)
Measured value <1.3× datasheet nominal; same-batch deviation <15% . Reference: approx. 0.56 mΩ (1kHz, 25°C, fully charged).
Step 4: Capacity confirmation
Capacity test at the 20hr current (I = 25.00A for a 400Ah battery); measured capacity ≥380Ah (95% of rating) accepted, <90% rejected. Charge the battery to full before warehousing.
Record: battery number / date / ambient temperature / OCV / resistance / capacity / conclusion / inspector signature — used for warranty claims and later string matching.
§18d. Safety and Compliance
VRLA batteries are maintenance-free, but hydrogen generation during charging, dilute sulfuric acid corrosion and high-current short-circuit risks require strict rules:
|
Level |
Meaning |
Typical situation |
|
DANGER |
Can cause injury or death |
Sealed enclosure use; non-specified charger; metal tools bridging terminals |
|
WARNING |
May cause injury or property damage |
Metal enclosure without insulation; near sparks; open flame; reversed polarity |
|
CAUTION |
May cause minor injury or damage |
Out-of-range temperature; near heat sources; damp environment; direct sunlight |
Prohibitions:
|
Prohibition |
Requirement |
Reason |
|
Mixing chemistries |
Do not mix with Ni-MH / Ni-Cd / lithium |
Leakage, heating, rupture |
|
Organic solvents |
Do not clean with thinner, petrol or grease |
Corrodes the housing |
|
Exceeding rated current |
Stay within datasheet maximum |
Leakage, heating, rupture |
|
Carrying by terminals |
Never lift by terminals or cables |
Damages the plate group |
|
Stepping on the battery |
No heavy objects or standing |
Deformation and internal short circuit |
|
Application |
Requirement |
Note |
|
Life-support medical equipment |
Requires an independent backup power system |
VRLA failure may endanger life |
|
Dialysis equipment |
Not recommended |
High reliability requirement; professional assessment |
|
Nuclear / defence equipment |
Prohibited |
Requires dedicated non-VRLA solutions |
|
Automotive / aircraft / rail / marine control |
Prohibited |
Precision control on moving platforms |
|
Subsea equipment |
Prohibited |
High humidity and pressure; severe leakage consequences |
|
Item |
Requirement |
Note |
|
Insulated tools |
PVC-taped wrench, one terminal at a time |
Prevents short circuit across terminals |
|
PPE |
Acid-resistant gloves, insulated boots, goggles |
Prevents shock, burns and acid splash |
|
Acid contact |
Rinse with plenty of water for 15 minutes |
Seek medical help; eye splash immediate |
|
Scrap disposal |
Licensed recycler per local regulations |
Lead recovery >95%; never dismantle |
|
Symptom |
Immediate action |
Note |
|
Swelling / deformation |
Stop use and isolate |
Precursor to thermal runaway |
|
Leakage / smoke |
Cut power, ventilate, evacuate |
Acid corrosion + hydrogen; do not wash with water |
|
Odour / abnormal heat |
Stop charging, disconnect load |
Check charger and polarity |
|
Abnormal cell voltage |
Check string balance |
Deviation >50mV requires balancing |
Restricted applications: life-support medical equipment requires an independent backup system; dialysis equipment is not recommended; nuclear/defence, automotive/aircraft/rail/marine control and subsea equipment are prohibited.
Emergency handling: swelling/deformation — stop use and isolate; leakage/smoke — cut power, ventilate, evacuate; odour/abnormal heat — stop charging and disconnect the load; abnormal cell voltage — check string balance.
This section is based on mainstream VRLA safety practice. Site procedures, local regulations (e.g. NFPA 70E / IEC 62485) and contract terms take precedence.
§19. CHISEN® Product Strength and Global Service
1. Product range
20+ years focused on VRLA; 200+ models covering 2V/4V/6V/12V, 1.3-3000Ah; mainstream models in stock, shipment in 7-15 days.
2. Global service
60+ export countries; telecom, power, data centre, PV, railway and medical projects; 7×24 multilingual support (EN/CN/ES/FR/AR/RU/VI).
3. Quality control
100% capacity / resistance / voltage / appearance inspection; SPC on paste mixing, group assembly, formation and sealing; third-party inspection on request.
4. Export support
Commercial invoice, packing list, CO, MSDS, sea transport hazard identification report and factory test report on request.
5. Long-term cooperation
Dedicated technical contact; lead sharing and training for OEM partners; annual rebates, priority supply and new-product trials for strategic customers.
6. Sustainability
Lead recovery >95%; RoHS/REACH declarations on request; destination environmental requirements handled per customer need.